Support span for Stainless Steel Piping system

Spans are based on uninsulated pipe filled with water.

Pipe support spans and deflections are in millimetres.

Maximum deflection specified is at center of span.

 

Dia mm Dia inches Pipe Schedule Support
Span
Maximum
Deflection
Support
Span
Maximum
Deflection
20 3/4 40s 3500 12.7 3000 6.35
25 1 40s 4000 12.7 3350 6.35
40 1 1/2 40s 4750 12.7 4000 6.35
50 2 10s 5100 12.7 4300 6.35
50 2 40s 5300 12.7 4450 6.35
80 3 10s 6100 12.7 5100 6.35
80 3 40s 6400 12.7 5400 6.35
100 4 10s 6700 12.7 5600 6.35
100 4 40s 7200 12.7 6000 6.35
150 6 10s 7850 12.7 6600 6.35
150 6 40s 8600 12.7 7200 6.35