Base Material: Reinforced
Thermosetting Resin (RTR)
Rating: Class 150 Service: Fire Water
Design Pressure: 12 bar 
Design Temp.: -29 to 93°C
Corrosion Allowance: 0mm
Item Size Rating/
Schedule
Ends/Dimensions Specification/Description
Pipe 2"-12" PN 12 Bell and spigot type
(adhesive bonded joint)
RTR, Filament Wound Pipes as per ASTM D2996
2"-12" PN 12 Bell and spigot type
(adhesive bonded joint)
Elbow 90° 2"-12" PN 12 Bell Ends
(adhesive bonded joint)
RTR, ASTM D5685
Elbow 45° 2"-12" PN 12 Bell Ends
(adhesive bonded joint)
RTR, ASTM D5685
Equal Tee 2"-12" PN 12 Bell Ends
(adhesive bonded joint)
RTR, ASTM D5685
Reducing
Tee
2"-12" PN 12 Bell Ends
(adhesive bonded joint)
RTR, ASTM D5685
Equal
Lateral 45°
2"-12" PN 12 Bell Ends
(adhesive bonded joint)
RTR, ASTM D5685
Concentric
Reducer
2"-12" PN 12 Bell Ends
(adhesive bonded joint)
RTR, ASTM D5685
Coupling 2"-12" PN 12 Socket Ends
(adhesive bonded joint)
RTR, ASTM D5685
Nipple 2"-12" PN 12 Spigot Ends
(adhesive bonded joint)
RTR, ASTM D5685
Flange 2"-12" PN 12, FF Socket Ends
(adhesive bonded joint) Drilling as per ASME B1.5
RTR, ASTM D4024
Blind
Flanges
2"-12" PN 12, FF

Blind. Drilling as per ASME B16.5

RTR, ASTM D4024
Spectacle Blind 2"-12" PN 12

Dimensions as per ASME B16.48

ASTM A516 Gr70 with Cu-Ni Overlay
Bolting All Sizes Stud Bolts: ASTM A193 B7 Bolts and ASTM A194 2H Nuts
Galvanized
Gasket 2"-12" CL 150 Full-face elastomeric, 50-60 SHORE A durometer,
3.2 mm thick or full-face neoprene gaskets 3-5mm thick, 60-70 SHORE hardness
Gate Valve 2"-12" CL 150 FF, Flanged Ductile iron ASTM A395 epoxy
lined body, BB, ASTM B61/B62
bronze trim (less than 16% zinc).

Notes:

  1. Structural wall thickness of pipes and fittings shall be as per the per Vendor standard to suit the applicable pressure/vacuum rating.
  2. The long-term hydrostatic strength of pipe shall be determined in accordance with Procedure-A or B of ASTM D2992. This shall be used to establish the pipe pressure rating. Pressure rating is the maximum long-term operating pressure recommended by the manufacturer.
  3. UV protection shall be provided for aboveground piping systems.

Reference ASTM Specifications

ASTM D2992 - Standard Practice for Obtaining Hydrostatic or Pressure Design Basis for “Fiberglass” (Glass-Fiber-Reinforced Thermosetting-Resin) Pipe and Fittings

ASTM D2996 - Standard Specification for Filament-Wound “Fiberglass” (Glass-Fiber-Reinforced Thermosetting-Resin) Pipe

ASTM D3567 - Standard Practice for Determining Dimensions of “Fiberglass” (Glass-Fiber-Reinforced Thermosetting Resin) Pipe and Fittings

ASTM D5685 - Standard Specification for “Fiberglass” (Glass-Fiber-Reinforced Thermosetting-Resin) Pressure Pipe Fittings

ASTM D4024 - Standard Specification for Machine Made “Fiberglass” (Glass-Fiber-Reinforced Thermosetting Resin) Flanges