Support span for Copper Alloy Piping systems
(14 and 20 barg systems)
Spans are based on the lesser of maximum stress value of 25N/mm² and
a maximum deflection of 6.35mm for all sizes.
Nom Dia (inches) |
Outside dia (mm) |
Maximum span between supports (mm) |
---|---|---|
1/2 | 16 | 1700 |
3/4 | 25 | 2000 |
1 | 30 | 2250 |
1 1/4 | 38 | 2500 |
1 1/2 | 44.5 | 2500 |
2 | 57 | 2750 |
Nom Dia (inches) |
Outside dia (mm) |
Maximum span between supports (mm) |
---|---|---|
3 | 76.1 | 3000 |
3 1/2 | 88.9 | 3250 |
4 | 108 | 3750 |
6 | 159 | 4500 |
8 | 219.1 | 5250 |
10-36 | 267-914 | 6000 |