Support span for Copper Alloy Piping systems
(14 and 20 barg systems)

Spans are based on the lesser of maximum stress value of 25N/mm² and
a maximum deflection of 6.35mm for all sizes.

Nom Dia
(inches)
Outside dia
(mm)
Maximum span
between supports (mm)
1/2 16 1700
3/4 25 2000
1 30 2250
1 1/4 38 2500
1 1/2 44.5 2500
2 57 2750

Nom Dia
(inches)
Outside dia
(mm)
Maximum span
between supports (mm)
3 76.1 3000
3 1/2 88.9 3250
4 108 3750
6 159 4500
8 219.1 5250
10-36 267-914 6000