Spans are based on pipe filled with water and maximum sag of 2.5mm at center of span.

Pipe support spans specified are in metres.

Nom Dia mm Nom Dia inches Support Span for Sch 40 PVC pipe
@ 60°F @ 100°F @ 140°F
15 1/2 1.3 1.2 1.15
20 3/4 1.35 1.3 1.2
25 1 1.5 1.45 1.35
40 1 1/2 1.7 1.6 1.5
50 2 1.75 1.7 1.6
50 2 1.9 1.8 1.75
80 3 2.3 2.1 2.05
100 4 2.5 2.35 2.3
150 6 2.9 2.75 2.6
200 8 3.2 3.05 2.95
250 10 3.5 3.35 3.2
300 12 3.8 3.55 3.4

 

Nom Dia mm Nom Dia inches Sch 80 PVC pipe
@ 60°F @ 100°F @ 140°F
15 1/2 1.35 1.2 1.15
20 3/4 1.45 1.35 1.3
25 1 1.6 1.5 1.45
40 1 1/2 1.75 1.65 1.6
50 2 1.8 1.75 1.68
50 2 1.95 1.9 1.8
80 3 2.4 2.25 2.1
100 4 2.65 2.5 2.4
150 6 3.2 3.05 2.9
200 8 3.5 3.35 3.2
250 10 3.85 3.7 3.5
300 12 4.25 4 3.8